  • 2 параллельная система ИБП

    1. parallel UPS system

     

    параллельная система ИБП
    -

    [Интент]

    Parallel Operation: The system shall have the option to install up to four (4) UPSs in parallel configuration for redundancy or capacity.
    1. The parallel UPS system shall be of the same design, voltage, and frequency. UPS modules of different size ratings shall be permitted to be paralleled together for purposes of increased capacity or UPS module redundancy. The UPSs in the parallel configuration shall not be required to have the same load capacity rating.
    2. Parallel Capacity: With N+0 system-level redundancy, up to 2MW of load can be supported by the system.
    3. Parallel Redundancy: With N+1 system-level redundancy, up to 1.5MW of load can be supported by the system, and only the UPS being replaced must be isolated from the source (bypass operation is not required for the entire system during the UPS replacement procedure).
    4. Output control: A load sharing circuit shall be incorporated into the parallel control circuits to ensure that under no-load conditions, no circulating current exists between modules. This feature also allows each UPS to share equal amounts of the total critical load bus. The output voltage, output frequency, output phase angle, and output impedance of each module shall operate in uniformity to ensure correct load sharing. This control function shall not require any additional footprint and shall be an integral function of each UPS. The static bypass switches shall be connected in parallel.
    5. Parallel System Controls: To avoid single points of failure, the UPS system shall have no single dedicated control system designed to control the operation of the parallel UPS system. Control of and direction of parallel UPSs shall take place via a master/slave relationship, where the first UPS to receive logic power asserts itself as a master. In the event of a master failure, a slave UPS shall take the role of master and assume the responsibility of the previous master UPS. Regardless of which UPS is master or slave, user changes to the system status, such as request for bypass, can be done from any UPS connected to the bus and all UPS on the bus shall transfer in simultaneously.
    6. Communication: Communication between modules shall be connected so that the removal of any single cable shall not jeopardize the integrity of the parallel communication system. Load sharing communications shall be galvanically isolated for purposes of fault tolerance between UPS modules. A UPS module's influence over load sharing shall be inhibited in any mode where the UPS inverter is not supporting its output bus. Transfers to and from bypass can be initiated from any online UPS in the system.
    7. Display: Each UPS multi-color LCD touch screen user interface shall be capable of using an active touch screen mimic bus to show the quantity of UPS(s) connected to the critical bus, as well as the general status of each UPS, such as circuit breaker status information. Any touchscreen display shall support the configuration of the [entire parallel] system and shall provide event and alarm data for all UPSs in the parallel configuration. A Virtual Display Application shall be available for download to the customer’s computer and shalll support remote monitoring of a complete system with up to 4 UPSs in parallel.
    8. Battery runtime: Each UPS must have its own battery solution. The battery solution for the entire system can be a combination of standard and third-party batteries, but each UPS must use only one battery solution – either standard or third-party batteries.
    9. Switchgear: A custom switchgear option shall be required for parallel operation.

    [Schneider Electric]

    Тематики

    EN

    Русско-английский словарь нормативно-технической терминологии > параллельная система ИБП

См. также в других словарях:

  • redundancy — noun (BrE) ADJECTIVE ▪ large scale, major, mass, massive ▪ The closure of the mine led to large scale redundancies. ▪ possible, threatened ▪ …   Collocations dictionary

  • avoid — verb 1 prevent sth; choose not to do sth ADVERB ▪ altogether ▪ It is sometimes impossible to avoid conflict altogether. ▪ actively, assiduously, carefully, consciously, deliberately …   Collocations dictionary

  • redundancy — [[t]rɪdʌ̱ndənsi[/t]] redundancies 1) N COUNT: usu pl When there are redundancies, an organization tells some of its employees to leave because their jobs are no longer necessary or because the organization can no longer afford to pay them. [BRIT] …   English dictionary

  • Logic redundancy — occurs in a a digital gate network containing circuitry that does not affect the static logic function. There are several reasons why logic redundancy may exist. One reason is that it may have been added deliberately to suppress transient… …   Wikipedia

  • Common Address Redundancy Protocol — The Common Address Redundancy Protocol or CARP is a protocol which allows multiple hosts on the same local network to share a set of IP addresses. Its primary purpose is to provide failover redundancy, especially when used with firewalls and… …   Wikipedia

  • Compiler optimization — is the process of tuning the output of a compiler to minimize or maximize some attributes of an executable computer program. The most common requirement is to minimize the time taken to execute a program; a less common one is to minimize the… …   Wikipedia

  • re·dun·dan·cy — /rıˈdʌndənsi/ noun, pl cies 1 a [noncount] : the act of using a word, phrase, etc., that repeats something else and is therefore unnecessary Avoid redundancy in your writing. 1 b [count] : a word, phrase …   Useful english dictionary

  • Otoplasty — Otoplasty: the pre operative front aspect (left), and the post operative front aspect (right) of an infantile otopexy (ear pinback) correction to a girl. Otoplasty (Greek ōtoûs, ear + plassein, to shape) denotes the surgical and non surgical… …   Wikipedia

  • abbreviation — /euh bree vee ay sheuhn/, n. 1. a shortened or contracted form of a word or phrase, used to represent the whole, as Dr. for Doctor, U.S. for United States, lb. for pound. 2. an act of abbreviating; state or result of being abbreviated; reduction… …   Universalium

  • Coxeter group — In mathematics, a Coxeter group, named after H.S.M. Coxeter, is an abstract group that admits a formal description in terms of mirror symmetries. Indeed, the finite Coxeter groups are precisely the finite Euclidean reflection groups; the symmetry …   Wikipedia

  • List of Catholic priests — This is an annotated list of men primarily known for their work as Catholic priests. Catholic priests who are mostly known for their non priestly work should be placed on other lists. Further men known for being bishops, archbishops, and other… …   Wikipedia

Поделиться ссылкой на выделенное

Прямая ссылка:
Нажмите правой клавишей мыши и выберите «Копировать ссылку»